ANALISIS KINERJA MINYAK TRANSFORMATOR KILN DRIVE 5W1W03T1 INDARUNG V PT. SEMEN PADANG

Fikrilla, Angga (2025) ANALISIS KINERJA MINYAK TRANSFORMATOR KILN DRIVE 5W1W03T1 INDARUNG V PT. SEMEN PADANG. S1 thesis, UNIVERSITAS UNJA.

[img] Text
Abstrak.pdf

Download (82kB)
[img] Text
BAB 1.pdf

Download (170kB)
[img] Text
BAB V.pdf

Download (114kB)
[img] Text
Cover Skirpsi.pdf

Download (141kB)
[img] Text
DAFTAR PUSTAKA.pdf

Download (119kB)
[img] Text
SKRIPSI_FULL_ANGGA FIKRILLA_M1A120039..pdf
Restricted to Repository staff only

Download (7MB)
[img] Text
lembar pengesahan.pdf

Download (647kB)
Official URL: https://repository.unja.ac.id/

Abstract

Pengujian tegangan tembus minyak tansformator merupakan upaya untuk mengetahui kemampuan isolasi minyak transformator tersebut, untuk pemeliharaan dan keamanan operasi transformator dalam sistem kelistrikan. Perlu dilakukan pengecekan dan perawatan terhadap minyak transformator yang bertujuan guna memastikan keamanan pada setiap pengoperasian transformator tersebut, penggunaan energi lebih optimal dan efesien. Penelitian ini menggunakan metode kuantitatif melalui observasi dalam pengambilan data. Metode ini digunakan untuk melakukan Evaluasi Hasil pengujian tegangan tembus minyak transformator, yang mencakup pemeriksaan isolasi listrik pada minyak transformator apakah sudah sesuai dengan Persyaratan Umum Instalasi Listrik (SPLN) yang berlaku di Indonesia dan IEC 60156-95 yang berlaku secara internasional. Penenlitian ini dilakukan di P.T SEMEN PADANG yang berlokasi di JL. Raya Indarung No.01 Padang 25237, Kota Padang Sumatera Barat. Hasil penelitian menunjukkan bahwa tegangan tembus minyak transformator sebelum dilakukan purifikasi atau pemurnian minyak transformator yaitu sebesar 16,7 kV dan 20,2 kV dan setelah dilakukan purifikasi nilai tegangan tembus minyak transformator tersebut menjadi 98,7 kV. Penilaian ini didasarkan pada kriteria yang telah ditentukan berdasarkan standar Persyaratan Umum SPLN dan IEC 60156-95. Diketahui penyebab rendah nya nilai tegangan tembus minyak transformator yaitu adanya kontaminan zat lain yang terkandung dalam minyak transformator yang disebabkan adanya kebocoran pada bagian bawah transformator, solusi nya yaitu melakukan perbaikan dengan cara mengganti seal transformator dan melakukan purifikasi minyak transformator (pemurnian). Kata Kunci : minyak transformator, Analisis kinerja minyak transformator atau nilai breakdown voltage, IEC 60156-95 dan SPLN. Testing the breakdown voltage of transformer oil is an effort to determine the insulating capability of the transformer oil, for maintenance and safe operation of the transformer in the electrical system. It is necessary to check and maintain transformer oil with the aim of ensuring safety in every operation of the transformer, making energy use more optimal and efficient. This research uses quantitative methods through observation in collecting data. This method is used to evaluate the results of the transformer oil breakdown voltage test, which includes checking the electrical insulation of the transformer oil to see whether it complies with the General Requirements for Electrical Installations (SPLN) which apply in Indonesia and IEC 60156-95 which applies internationally. This research was carried out at P.T SEMEN PADANG which is located on JL. Raya Indarung No.01 Padang 25237, Padang City, West Sumatra. The aim of this research is to determine the suitability of transformer oil by testing the breakdown voltage of the transformer oil. The results of the research show that the transformer oil breakdown voltage before purification of the transformer oil is 16.7 kilo volts and 20.2 kilo volts and after purification the transformer oil breakdown voltage value is 98.7 kilo volts. This assessment is based on criteria that have been determined based on the SPLN General Requirements standard and IEC 60156-95. It is known that the cause of the low breakdown voltage value of transformer oil is the presence of other contaminant substances contained in the transformer oil which is caused by a leak at the bottom of the transformer. The solution is to repair it by replacing the transformer seal and purifying the transformer oil (purification). Keywords: transformer oil, evaluation of breakdown voltage values, IEC 60156-95 and SPLN.

Type: Thesis (S1)
Subjects: L Education > L Education (General)
Divisions: Fakultas Teknik > Teknik Elektro
Depositing User: FIKRILLA
Date Deposited: 07 Jul 2025 06:52
Last Modified: 07 Jul 2025 06:52
URI: https://repository.unja.ac.id/id/eprint/81409

Actions (login required)

View Item View Item